Wire the power supply – Rockwell Automation 2711P-RSACDIN AC Power Supply User Manual
Page 7

AC Power Supply for PanelView Plus/PanelView Plus CE Terminals 7
Publication 2711P-IN005C-EN-P - March 2007
Wire the Power Supply
Terminals A, B and C are 120/230V supply terminals. Terminals D, E and F are
available to daisychain this 120/230V power to other 2711P-RSACDIN power
supplies.
Torque screw terminals to 5-7 lb-in (0.5 - 0.6 Nm) when making connections.
1. Connect the 120/230V ac power to the left side terminals on the connectors
on the left side of the module as follows:
2. Connect terminal G or J (+24V dc) to the +24V dc terminal on the PanelView
Plus/PanelView Plus CE.
3. Connect terminal H or I (+24V dc common) to the +24V dc common
terminal on the PanelView Plus/PanelView Plus CE.
The remaining two 24V terminals should remain unconnected.
IMPORTANT
Input and output wiring must be in accordance with Class I, Division 2 wiring
methods per Article 501-4(b) of the National Electrical Code and in accordance
with the authority having jurisdiction.
Connect
To
ac Ground
GR
A
120/230V ac common
L2/N
B
120/230V ac power
L1
C
ATTENTION
The total length of wire for terminals H, I, J and G must not exceed 3 m.
Exceeding the 3 m length can reduce noise immunity.
(GR) A
(L2/N) B
(L1) C
F
G
E D
H
I
J
24V DC
POWER SUPPLY
2711P-RSACDIN
24V
COM
POWER
PanelView Plus