Rockwell Automation 1799-D12G12GL 12 Input/12 Output Discrete Embedded I/O User Manual
Page 20

20
12 Input/12 Output Discrete Embedded TTL I/O Module with Pulse Width Modulation and DeviceLogix
Publication 1799-IN008A-EN-P - July 2005
General Specifications (continued)
EFT/B Immunity
IEC 61000-4-4:
±2kV at 2.5kHz on signal ports
±2kV at 5kHz on communications ports
Surge Transient Immunity
IEC 61000-4-5:
±2kV line-earth (CM) on communications ports
Conducted RF Immunity
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz...80MHz
Enclosure Type Rating
None (open-style)
5V Supply Voltage Ranges
4.8...5.1V
0...5.1V dc
Supply Power/Current Ratings
Isolated outputs limited to 1 volt-ampere in each ungrounded output
line
Power Consumption
11.25 VA dc
Power Dissipation
11.25 VA dc @ 70
°C, approximate minimum enclosure size 229 mm x
165 mm x 127 mm (9 in. x 6.5 in. x 5 in.)
Isolation Voltage
(continuous-voltage withstand
rating)
50V continuous
Tested to withstand 2000V dc for 60 seconds
Conductors Wire Size
I/O: 20 AWG (0.5mm2)...26 AWG (0.13mm
2
) solid or stranded copper
wire rated at 75 °C or greater 1.2 mm (3/64 in.) insulation maximum.
DeviceNet: 14 AWG (2.5mm
2
)...22 AWG (0.25mm
2
) solid or stranded
copper wire rated at 75 °C or greater 1.2 mm (3/64 in.) insulation
maximum. (Refer to publication DNET-UM072).
Wiring Category
1,2
2 - on signal ports
2 - on communications ports
Wire Type
Copper
1
Use this Conductor Category information for planning conductor routing. Refer to Publication 1770-4.1,
Industrial Automation Wiring and Grounding Guidelines.
2
Use this Conductor Category information for planning conductor routing as described in the appropriate
System Level Installation Manual.