PROFIBUS DP Communications

32

Publication 2711-6.3

The Node Address downloaded with the PanelView application file
will overwrite the current terminal setting. You can set a new
terminal address by using the terminal PROFIBUS DP screen,
however, the new address will take affect only after the terminal is
reset.

!

ATTENTION: The PROFIBUS DP protocol
mechanisms do not provide the ability to detect and
report a duplicate node address between a DP Master
and DP slave device, or between two DP slaves (only
between two DP Masters).

Note: The following procedure assumes the use of a keypad
terminal. If you have a PanelView with a touch screen, touch the
displayed item you want to change.

To manually change the node address:

1. Press [F8].

The numeric entry scratchpad is displayed.

2. Enter the new address in the scratchpad and press the Enter key.

3. Verify that the correct address is displayed in the New Address

field.

4. Press [F1] to restart the terminal.

The terminal will restart with the new address.

5. Both the current and new address fields will display the new

address setting.

Changing the Node
Address