Rockwell Automation 7000 PowerFlex Medium Voltage Air-Cooled (B Frame) Installation - ForGe Control User Manual
Page 92
92
Rockwell Automation Publication 7000-IN007E-EN-P - June 2014
Appendix D
Specifications
Number of Inverter SGCTs
Voltage
SGCTs (per phase)
2400V
3300V
4160V
6600V
2
4
4
6
Inverter PIV Rating
(Peak Inverse Voltage)
Voltage
PIV (each device) Total PIV
2400V
3300V
4160V
6600V
6500V
6500V
6500V
6500V
6500V
13,000V
13,000V
19,500V
Rectifier Designs
Direct-to-Drive (transformerless AFE rectifier)
AFE with separate isolation transformer
18 Pulse with separate isolation transformer
Rectifier Switch
SCR (18 Pulse), SGCT (AFE Rectifier)
Rectifier Switch Failure Mode
Non-rupture, Non-arc
Rectifier Switch Failure Rate (FIT)
50 (SGCT) 100 (SCR) per 1 Billion Hours Operation
Rectifier Switch Cooling
Double Sided, Low Thermal Stress
Number of Rectifier Devices per phase Voltage
AFE
18 Pulse
2400V
3300V
4160V
6600V
2
4
4
6
6
6
6
6
Output Current THD (1
st
…49
th
)
< 5%
Output Waveform to Motor
Sinusoidal Current / Voltage
Medium Voltage Isolation
Fiber Optic
Modulation techniques
Selective Harmonic Elimination (SHE)
Synchronous Trapezoidal PWM
Asynchronous or Synchronous SVM (Space Vector Modulation)
Control Method
Digital Sensorless Direct Vector
Full Vector Control with Encoder Feedback (Optional)
Tuning Method
Auto Tuning via Setup Wizard
Speed Regulator Bandwidth
1...10 rad/s with standard control
1...20 rad/s with HPTC (optional)
Torque Regulator Bandwidth
15...50 rad/s with standard control
80...100 rad/s with HPTC (optional)
Torque Accuracy with HPTC (optional)
+/- 5%
Speed Regulation
0.1% without Encoder Feedback
0.01...0.02% with Encoder Feedback
Acceleration/Deceleration Range
Independent Accel/Decel – 4 x 30 s
Acceleration/Deceleration Ramp
Rates
4 x Independent Accel/Decel
S Ramp Rate
Independent Accel/Decel – 2 x 999 s
Critical Speed Avoidance
3 x Independent with Adjustable bandwidth
Stall Protection
Adjustable time delay
Table 16 - General Design Specifications (Continued)
Description