Switch 2, Legacy communications board kit – Rockwell Automation 2706-P92C_P94C InView Message Display User Manual
Page 13

InView Marquee Message Display 13
Publication 2706-IN016D-EN-P - February 2009
Switch 2
Switch 2 is used to set the serial address of the display. Position 1 is the LSB of the
address and position 8 is the MSB of the address.
•
If position 1 is on and all other positions are off, the display address will be
1.
•
If position 8 is on and all other positions are off, the display address will be
128.
•
If all positions are set to off, the serial address can be set using the InView
Messaging software.
The dip switch setting takes priority over the software setting. If the serial address is
set to 2 using the software (all the dip switches set to off) and then switch 2 is used
to set the serial address to 3 (position 1 and 2 set to on and the remaining positions
set to off), the serial address will then be 3. Also, once Switch 2 is used to set the
serial address and then all switch positions are set to off, the serial address setting
remains until it is changed by software or the dip switch is set.
Legacy Communications Board Kit
There is an optional Legacy Communications Board Kit available for the P9 series
displays. There are a total of six board kits: Remote I/O, DH+, DH-485, ControlNet,
DeviceNet, and EtherNet/IP. The Legacy Communications Board Kit converts the six
protocols to RS-232. The board kit mounts on the four PEM spacers that are
Switch
1
2
3
4
5
6
7
8
Value
1
2
4
8
16
32
64
128
RS485
Echo
Not
Used
Size
ON = P92C
OFF = P94C
Not
Used
ON = Disable
Download
Message
ON =
Diagnostics
Display Address
LSB
MSB
Baud Rate
3 4
OFF OFF = Software Default
ON OFF = 9600
OFF ON = 19200
ON ON = 38400