Rockwell Automation 61C345 4 Input 4-20mA Analog Rail Module User Manual
Page 21
3Ć7
Step 12. Attach the original 12Ćpoint and 4Ćpoint connectors with
wiring to the faceplate of the module. Use the stud
marked GND" (ground) on the bottom right flange of the
module to connect a ground wire.
Step 13. Set the Mode" switch on the faceplate to the desired
position.
Step 14. Connect the I/O Rail cable between the Analog Rail
connection labeled Input" and any rail connector on the
Reliance device that will communicate with the module.
Turn on power to the Reliance device connected to the
Analog Rail module. Recall that the Mode switch is read
each time the Reliance device connected to the module is
powered up. If applicable, reĆconnect the cable between
the Local I/O Head, or the DCS 5000/AutoMax Remote
I/O Head, and the host.
Step 15. Turn on power to the Analog Rail module Input Power"
connections.
Step 16. Turn on power to the external hardware connected to the
Analog Rail module.
Step 17. Verify that the hardware has been installed correctly.
For AutoMate systems, use the APX Point Monitor
function to test the module. To test the input channels,
verify that the input signal in the channel (4Ć20mA) is
proportional to an ammeter reading at the terminal points.
For DCS 5000, AutoMax, or Distributed Power DĆC Drive
systems, use the DCS 5000 or AutoMax Programming
Executive software I/O Monitor function, respectively. To
test the input channels, verify that the input signal in the
channel (4Ć20mA) is proportional to an ammeter reading
at the terminal points.