Rockwell Automation 61C345 4 Input 4-20mA Analog Rail Module User Manual
Page 17
3Ć3
Step 2.
If the power supply you are using is 24 VDC, replace the
factoryĆinstalled .25A fuse with the .75A fuse that came in
the shipping box with the module. Use a screwdriver to
release the fuse holder located on the Analog Rail
module faceplate. Pull the fuse holder out of the module.
Take the .25A fuse out of the fuse holder and replace it
with the .75A fuse. ReĆinsert the fuse holder into the
module. Turn the screwdriver clockwise while pressing
down on the fuse holder. The fuse holder must be flush
against the faceplate.
Step 3.
Mount the Analog Rail on the panel and attach it securely
to the wall with #10 (M5) studs or bolts.
Step 4.
Make certain that no voltage is present on the wires that
will be used to provide 120 VAC or 24 VDC power to the
Analog Rail module. Use either a 120 VAC or 24 VDC
power supply, but not both.
Step 5.
Using 14 AWG wire, connect input power to the screw
terminals on the Input Power" plug connector on the
faceplate as shown below. Strip off approximately 5/16"
of insulation from the wires.
24 VDC Power
Signal
Terminal Label
Terminal Number
24 VDC -
DC-
1
24 VDC +
DC+
2
120 VAC Power
Signal
Terminal Label
Terminal Number
120 VAC - (neutral)
L2/N
3
120 VAC + (hot)
L1
4
Step 6.
Use the stud marked GND" (ground) on the bottom right
flange of the module to connect a ground wire.
DANGER
THE USER IS RESPONSIBLE FOR CONFORMING WITH THE NATIONAL
ELECTRICAL CODE AND ALL OTHER APPLICABLE LOCAL CODES. WIRING
PRACTICES,
GROUNDING,
DISCONNECTS,
AND
OVERĆCURRENT
PROTECTION ARE OF PARTICULAR IMPORTANCE. FAILURE TO OBSERVE THIS
PRECAUTION COULD RESULT IN SEVERE BODILY INJURY OR LOSS OF LIFE.
Step 7.
Turn off all power to any external hardware that will
provide input signals to the module or be powered by the
module.
Step 8.
Attach a retainer clip to the connector at each end of the
I/O Rail cable (M/N 45C5). Note that faceplate connectors
have slots that correspond to the part of the retainer clip
that protrudes away from the cable connector. The
retainer clip is used to assure a tight connection between
the cable and faceplate connectors.
Step 9.
Using 14Ć22AWG wire, connect external hardware to the
Analog Inputs" plug connector on the faceplate as
shown below. Strip off approximately 5/16" insulation
from the wires.