And i, Or v, And l – Rockwell Automation 1797-OB4D FLEX Ex 24V DC Nonisolated Source 4 Output Module User Manual
Page 27: Of the associated apparatus are greater than c
FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module 27
Publication
1797-5.6 - June 2011
The entity concept allows interconnection of intrinsically safe apparatus
with associated apparatus not specifically examined in combination as a
system when the approved values of V
oc
and I
sc
or V
t
and I
t
of the associated
apparatus are less than or equal to V
max
and I
max
of the intrinsically safe
apparatus and the approved values of C
a
and L
a
of the associated apparatus
are greater than C
i
+ C
cable
and L
i
+ L
cable
respectively for the intrinsically safe
apparatus.
Terminal Connections
Terminals
V
t
(V)
I
t
(mA)
Groups
C
a
(
μF)
L
a
(
μH)
Male bus
connector
5.8
400
A…G
3.0
3.0
Hazardous (Classified) Location
Class I, Zones 0, 1, & 2 Groups IIC, IIB, IIA
Class I, Div. 1 & 2 Groups A, B, C, D
Class II, Div. 1 & 2 Groups E, F, G
Class III, Div. 1 & 2
Hazardous (Classified) Location
Class I, Zones 1 Groups IIC, IIB, IIA
Class I, Div. 1 Groups A, B, C, D
For connection to other
modules refer to the General
FM Certification Information
on page 29-1 of
.
From FM approved devices,
For connection to other
modules refer to the General
FM Certification Information on
page 29-1
.
1797-OB4D
16
Shield connection only
50
51
35
34
V
max
=5.8V
I
max
=400mA
C
i
=1350nF
L
i
=negligible
V
max
=9.5V
I
max
=1A
C
i
=negligible
L
i
=negligible
Male Bus
Connector
33
40
41
42
43
44
45
0 (+)
Female Bus
Connector
1 (-)
ch0
ch1
ch2
ch3
4 (+)
5 (-)
8 (+)
9 (-)
12 (+)
13 (-)
42059
Any Simple Apparatus or FM
approved device with Entity Concept
parameters (V
max
, I
max
, C
i
, L
i
)
appropriate for connection to
associated apparatus with Entity
Concept parameters listed in the table,
Terminal Connections.