24 FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module

Publication

1797-5.6 - June 2011

The values of L

o

and C

o

listed in the table above are allowed if one of the

following conditions is met:

• The total L

i

of the external circuit (excluding the cable) is < 1% of the

L

o

value or

• The total C

i

of the external circuit (excluding the cable) is < 1% of the

C

o

value.

The values of L

o

and C

o

listed in the table above shall be reduced to 50%

when both of the following conditions are met:

• The total L

i

of the external circuit (excluding the cable) is ≥ 1% of the

L

o

value, and

• The total C

i

of the external circuit (excluding the cable) is ≥ 1% of the

C

o

value.

Note: The reduced capacitance of the external circuit (including cable) shall
not be greater than 1µF for IIB and IIA and 600nF for IIC.



Simple apparatus is defined as a device which neither generates nor stores

more than 1.2V, 0.1 A, 20

μ

J, or 25 mW.



Wiring methods must be in accordance with the National Electric Code,

ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA
C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA
RP12.6.



This module, 1797-OB4D, must be used with terminal base 1797-TB3 or

1797-TB3S.



Terminals 2, 3, 6, 7, 10, 11, 14, 15, 17 to

32, 36 to 39, and 46 to

49 shall

not be connected.

WARNING:

Substitution of components may impair intrinsic safety.

AVERTISSEMENT: La substitution de composant peut compromettre la
securite intrinseque.

FM I/O Entity Parameters

If this product has the FM mark, it has been designed, evaluated, tested, and
certified to meet the following standards: