24 FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module
Publication
1797-5.6 - June 2011
The values of L
o
and C
o
listed in the table above are allowed if one of the
following conditions is met:
• The total L
i
of the external circuit (excluding the cable) is < 1% of the
L
o
value or
• The total C
i
of the external circuit (excluding the cable) is < 1% of the
C
o
value.
The values of L
o
and C
o
listed in the table above shall be reduced to 50%
when both of the following conditions are met:
• The total L
i
of the external circuit (excluding the cable) is ≥ 1% of the
L
o
value, and
• The total C
i
of the external circuit (excluding the cable) is ≥ 1% of the
C
o
value.
Note: The reduced capacitance of the external circuit (including cable) shall
not be greater than 1µF for IIB and IIA and 600nF for IIC.
Simple apparatus is defined as a device which neither generates nor stores
more than 1.2V, 0.1 A, 20
μ
J, or 25 mW.
Wiring methods must be in accordance with the National Electric Code,
ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA
C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA
RP12.6.
This module, 1797-OB4D, must be used with terminal base 1797-TB3 or
1797-TB3S.
Terminals 2, 3, 6, 7, 10, 11, 14, 15, 17 to
32, 36 to 39, and 46 to
49 shall
not be connected.
WARNING:
Substitution of components may impair intrinsic safety.
AVERTISSEMENT: La substitution de composant peut compromettre la
securite intrinseque.
FM I/O Entity Parameters
If this product has the FM mark, it has been designed, evaluated, tested, and
certified to meet the following standards: