Field wiring connections, Wire the outputs, Specifications – Rockwell Automation 2085-OW8_OW16 Micro800 8-Point and 16-Point AC/DC Relay Output Modules User Manual
Page 9: General specifications

Micro800 8-Point and 16-Point AC/DC Relay Output Modules 9
Publication 2085-IN004A-EN-P - September 2012
Field Wiring Connections
In solid-state control systems, grounding and wire routing helps limit the effects of noise due to
electromagnetic interference (EMI).
Wire the Outputs
Included with your 2085-OW8 module is a single 12-pin Removable Terminal Blocks (RTB).
Included with your 2085-OW16 module are two 12-pin RTB. Basic wiring of your module is
shown below.
Basic Wiring to the Module
Specifications
ATTENTION: Do not wire more than 2 conductors on any single terminal.
General Specifications
Attribute
2085-OW8
2085-OW16
Number of Outputs
8
16
Dimensions
HxWxD
28 x 90 x 87 mm
(1.10 x 3.54 x 3.42 in.)
44.5 x 90 x 87 mm
(1.75 x 3.54 x 3.42 in.)
Shipping weight, approx.
140 g (4.93 oz)
220 g (7.76 oz)
Wire size
0.25... 2.5 mm
2
(22...14 AWG) solid or stranded copper wire rated at 75 °C (167 °F ), or greater,
1.2 mm (3/64 in.) insulation max
CM0
O-00
O-01
CM1
O-02
O-03
CM2
O-04
O-05
CM3
O-06
O-07
L1 or +DC
L2 or -DC
45310
CM0
O-00
O-01
CM1
O-02
O-03
CM2
O-04
O-05
CM3
O-06
O-07
CM4
L1 or +DC
L2 or -DC
O-08
O-09
CM5
O-10
O-11
CM6
O-12
O-13
CM7
O-14
O-15
45311
2085-OW8
2085-OW16
Terminal Block 1
Terminal Block 2