beautypg.com

Certifications, Environmental specifications – Rockwell Automation 2085-OW8_OW16 Micro800 8-Point and 16-Point AC/DC Relay Output Modules User Manual

Page 11

background image

Micro800 8-Point and 16-Point AC/DC Relay Output Modules 11

Publication 2085-IN004A-EN-P - September 2012

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g

Shock, non-operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g DIN rail mount
35 g Panel mount

Emissions

CISPR 11
Group 1, Class A

ESD immunity

IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:
±2 kV at 5 kHz on signal ports

Surge transient immunity

IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports

Conducted RF immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications

Certification (when product
is marked)

(1)

Value

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and

Canada. See UL File E334470.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

European Union 2006/95/EC LVD, compliant with:

EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with:

Article 58-2 of Radio Waves Act, Clause 3

(1)

See the Product Certification link at

http://www.rockwellautomation.com/products/certification/

for Declaration of Conformity, Certificates, and

other certification details.

Environmental Specifications

Attribute

Value