Rockwell Automation 2361 Snubber Assembly Replacement User Manual
Page 4

4
Snubber Assembly Replacement (for 1250 and 1650A 1395 DC Drives)
Publication 2361-5.14 - July 1998
Removing the Assembly
1.
Using a voltmeter, test the voltage across the three phases, then
across the heatsink assembly and snubber assembly components.
2.
Unplug the thermoswitch connector (upper assemblies only).
Note: Unplug thermoswitch connectors for any other assemblies
if they are in the way.
3.
Unplug the gate lead connector from J1 on each armature-pulse
transformer board.
Note: Unplug gate lead connectors for any other assemblies if
they are in the way.
4.
Remove the two fuses from the front of the assembly.
5.
Remove the mounting bolts from the top and bottom of the
assembly.
6.
Lift the heatsink assembly out of the drive.
!
ATTENTION: If there is any voltage present, remove
the source of the voltage and check for voltages again
before proceeding to the next step.
!
ATTENTION: Heatsink assemblies weigh a about 60-
75 lbs each. Take proper precautions, following your
company’s material handling procedures, when lifting
to avoid injury and equipment damage.