beautypg.com

Specifications – Rockwell Automation 1757-PLX52 ProcessLogix Controller Module Installation Instructions User Manual

Page 12

background image

12 ProcessLogix Controller

Publication 1757-IN901D-EN-P - May 2007

Specifications

ProcessLogix Controller - 1757-PLX52

Attribute

Value

Intrinsically safe

No

Temp. rate of change

≤ 1 °C/min (≤ 33.8 °F/min)

Corrosives

G2 std, G3 option (ISA S71.04)

Emissions

CISPR 11:

Group 1, Class A

ESD immunity

IEC 61000-4-2:

4 kV indirect contact discharges

Radiated RF immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80%AM from 80

…2000 MHz

Power requirements

24V dc @ 5 mA

5.1V dc @ 1.6 A

3.3V dc @ 1.3 A

1.2V dc @ 7 mA

Controller battery backup time

Lithium battery

(standard, built in)

144 hours (non-rechargeable) - 6 days:

Replacement Battery: 1757-PLXBAT

Lithium battery is disconnected during shipment.

Battery Extension Module,
1757-BEM

120 hours (rechargeable) - 5 days

Spare Battery: 1757-BEMS

Removal/Insertion under power
(RIUP)

Permitted when equipment is installed in ordinary, non-hazardous,
locations (I/O modules reload automatically).

Not permitted when equipment is installed in a Class I, Division 2,
Hazardous (Classified) Location.