Rockwell Automation 1771-IAN 120V Input Module Installation Instructions User Manual
Page 12

AC (120V) Input Module
12
Publication 1771-IN032B-EN-P - July 2002
Emissions
CISPR 11
Group 1, Class A (with appropriate enclosure)
Enclosure Type Rating
None (open-style)
Keying
Between 16 and18
Between 20 and22
FieldWiring Arm
1771ĆWN
Wiring Arm Screw Torque
9 pound-inches (1.0Nm)
Certifications
(when product is marked)
UL
UL ListedIndustrial Control Equipment
CSA
CSA CertifiedProcess Control Equipment
CSA
CSA CertifiedProcess Control Equipment for Class I,
Division 2 Group A, B, C, D Hazardous Locations
CE
3
European Union 89/336/EEC EMC Directive,
compliant with:
EN 61000-6-4, Industrial Emissions
EN 50082-2, Industrial Immunity
EN 61236, Meas./Control/Lab., Industrial
Requirements
EN 61000-6-2, Industrial Immunity
European Union 73/736/EEC EMC Directive,
compliant with:
EN 61131-2, Programmable Controllers
C-Tick
3
Australian Radiocommunications Act, compliant with:
AS/NZS 2064, Industrial Emissions
1
14 gauge wire connectedto all terminals may not allow the cover on the fieldwiring arm to close. A smaller gauge wire may
be used.
2
You use this conductor category information for planning conductor routing as described in publication 1770Ć4.1, Industrial
Automation Wiring and Grounding Guidelines.
3
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates and other certification details
Publication 1771-IN032B-EN-P - July 2002
Supersedes Publication 1771-5.32 - October 1995
PN957678-76