Specifications – Rockwell Automation 1771-IAN 120V Input Module Installation Instructions User Manual
Page 11
![background image](/manuals/579949/11/background.png)
Specifications
AC (120V) Input Module
11
Publication 1771-IN032B-EN-P - July 2002
Inputs per module
32 (4 groups of 8)
Module Location
1771-A1B thru -A4B I/O Chassis
Voltage Range
85 to 135V ac, 50/60Hz
Nominal Input Voltage
120V ac
Nominal Input Current
8.2mA @ 115V ac, 60Hz
6.8mA @ 115V ac, 50Hz
Minimum On-state Current
5.2mA @ 85V ac, 60Hz
4.2mA @ 85V ac, 50Hz
Maximum Off-state Current
2.3mA @ 30V ac, 60Hz
1.9mA @ 30V ac, 50Hz
Maximum Off-state Voltage
30V ac
Input Impedance
0.2uF in parallel with 200K ohms (13.3K ohms @ 60Hz)
Input Signal Delay
Off to On: 10.0ms (+7ms)
On to Off: 20.0ms (+15ms)
Isolation Voltage
Testedto withstand 1000V for 60s.
Power Dissipation
4.5W (max); 1.0W (min)
Thermal Dissipation
15.4 BTU/hr (max); 3.4 BTU/hr (min)
Backplane Current
280mA @ 5V dc maximum
Conductors
Wire Size
Category
14-22 AWG (2.5-0.25mm
2
) (max)
1
stranded copper rated at
60
o
or greater
3/64 inch (1.2mm) insulation (max)
2
1
Environmental Conditions
Operating
Temperature
IEC 60068-2-1 (Test Ad, Operating Cold)
IEC 60068-2-2 (Test Bd, Operating Dry Heat)
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
32 to 140°F (0
o
to 60
o
C)
Storage Temperature
IEC 60068-2-1 (Test Ab, Unpackaged, Nonoperating Cold)
IEC 60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry Heat)
IEC 60068-2-14 (Test Na, Unpackaged, Nonoperating Thermal
Shock)
-40 to 185°F (-40 to 85
o
C)
Relative Humidity
IEC 60068-2-30 (Test Db, Unpackaged, Nonoperating Damp
Heat)
5 to 95%, noncondensing
Shock
Operating
Nonoperating
IEC 60068-2-27 (Test Ea, UnpackagedShock)
30g
50g
Vibration
IEC 60068-2-6 (Test Fc, Operating)
2g @ 10-500Hz
ESD Immunity
IEC 61000-4-2
4kV indirect discharges
Radiated RF Immunity
IEC 61000-4-3
10V/m, with 1kHz sine-wave 80% AM from 30MHz to 1000MHz
EFT/B Immunity
IEC 61000-4-4
+1kV @ 5kHz on signal ports
Surge Transient Immunity
IEC 61000-4-5
+1kV line-line (DM) and+2kV line-earth (CM) on signal ports
Conducted RF Immunity
IEC 61000-4-6
10V rms with 1kHz sine wave 80% AM from 150kHz to 30MHz