Controlnet network channel status indicators – Rockwell Automation 1756-CNB ControlLogix ControlNet Bridge Module, Series E Installation Instructions User Manual
Page 28
28 ControlLogix ControlNet Interface Module
Publication
1756-IN604A-EN-P - February 2006
ControlNet Network Channel Status Indicators
The ControlNet network channel status indicators appear in one of the
following states:
• Steady - indicator is on continuously in the defined state.
• Alternating - the two indicators alternate between the two defined
states at the same time (applies to both indicators viewed together).
The two indicators are always in opposite states, out of phase.
• Flashing - the indicator alternates between the two defined states
(applies to each indicator viewed independent of the other). If both
indicators are flashing, they must flash together, in phase.
The ControlNet Network Channel Status Indicators table summarizes the
meanings of these states.
ControlNet Network Channel Status Indicators
Cause
Action
Off
No power
None or power up.
Steady red
Faulted unit
Cycle power or reset unit.
If fault persists, contact A-B
representative or distributor.
Alternating
red/green
Self-test
None
Alternating red/off Incorrect node configuration
Check network address and other
ControlNet network configuration
parameters.
Cause
Action
Off
Channel disabled
Program network for redundant
media, if required.
Steady green
Normal operation
None
Flashing green/off Temporary errors
None; unit will self-correct.
and
A
B
or
A
B