Rockwell Automation 1756-CNB ControlLogix ControlNet Bridge Module, Series E Installation Instructions User Manual
Page 25

ControlLogix ControlNet Interface Module 25
Publication
1756-IN604A-EN-P - February 2006
Red
DUPL
NODE
For a redundant system this may
be a temporary condition during
chassis switchover. Otherwise,
the module’s network address is
the same as another module’s on
the link.
1. (For redundant systems only.)
Wait 10 seconds; if the
condition persists, perform the
following steps:
2. (Optional, see page 12.)
Turn chassis power supply off.
3. Remove the module from the
chassis.
4. Set the network address
switches to a unique address
(01-99).
5. Install the module in the
chassis.
6. If off, turn chassis power
supply on.
RACK
ERR
Cannot read backplane EEPROM,
or rack/slot address incorrect
Replace the chassis.
STOP
The module commanded to stop
functioning by the redundancy
module. This occurs when a
nonredundancy compliant
module is placed into a
redundant secondary chassis.
Remove nonredundancy compliant
module from redundant secondary
chassis and replace with
redundancy compliant module.
WAIT
SRM
(2)
The module waiting for the
redundancy module to complete
power-up.
None required.
Flashing
Red
BOOT
The module has invalid
firmware.
Update module firmware with
ControlFlash Update Utility.
ROM
UPDT
Flash update is in progress.
None required.
SNGL
KPR!
The module detected that it has
been connected to a ControlNet
1.5 (single-keeper) network.
Update the module’s firmware at
MAC ID 01 and reschedule the
network.
Module Status Indicator LED and Module Status Display
LED
Display
Cause
Action
OK