Rockwell Automation 1771-OAN Installation Instructions User Manual
Page 12
![background image](/manuals/579897/12/background.png)
AC (120/240V) Output Module
12
Publication 1771ĆIN031B-EN-P - November 2002
Specifications - ac (120-240V) Output Module, Cat. No. 1771-OAN
Emissions
CISPR 11
Group 1, Class A (with appropriate enclosure)
Enclosure Type Rating
None (open style)
Keying
Between 16 and 18
Between 22 and 24
Fuses
Four 4.0A, 250V normal blow fuses (1 per group)
Field Wiring Arm
Cat. No. 1771-WN
Field Wiring Arm Screw Torque
7-9 pound-inches (0.7-1.0Nm)
Conductors
Wire Size
Category
14-22AWG (2.5-0.25mm
2
) stranded copper wire rated at 60
o
C
or greater
3/64 inch (1.2mm) insulation (max)
1
1
Certifications
(when product is marked)
UL
UL Listed Industrial Control Equipment
CSA
CSA Certified Process Control Equipment
CE
2
European Union 89/336/EECEMCDirective,
compliant with:
EN 61000-6-4, Industrial Emissions
EN 50082-2, Industrial Immunity
EN 61326, Meas./Control/Lab., Industrial
Requirements
EN 61000-6-2, Industrial Immunity
European Union 73/23/EECLVD Directive,
compliant with:
EN 61131-2, Programmable Controllers
C-Tick
2
Australian Radiocommunications Act,compliant
with AS/NZS 2064, Industrial Emissions
1 Use this conductor category information for planning conductor routing . Refer to publication 1770Ć4.1, Industrial Automation Wiring and
Grounding Guidelines."
2 See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Publication 1771ĆIN031B-EN-P - November 2002
Supersedes publication 1771Ć5.31 - October 1995
PN957678-75