Environmental Specifications
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…60 °C (-4…140 °F)
Temperature, storage
IEC 60068-2-1 (Test Ab, unpackaged nonoperating cold),
IEC 60068-2-2 (Test Bb, unpackaged nonoperating dry heat):
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30g
Shock, non-operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50g
Vibration
IEC 60068-2-6 (Test Fc, Operating): 5g @ 10...500 Hz
Emissions
CISPR 11: Group 1, Class A
ESD immunity
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80%AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100%AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz
3V/m with 1 kHz sine-wave 80%AM from 2000...2700 MHz
EFT/B immunity
IEC 61000-4-4:
±3kV at 5 kHz on signal ports
Surge transient
immunity
IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF
immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from 150 kHz...80 MHz