Hazardous location considerations, Explosion hazard – Rockwell Automation 1763-L16xxx MicroLogix 1100 Programmable Controllers Installation Instructions User Manual
Page 8

8
Publication 1763-IN001B-EN-P - September 2007
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or
non-hazardous locations only. The following WARNING statement applies to use in
hazardous locations.
Catalog
Number
Description
Input
Power
Digital
Inputs
Analog
Inputs
Digital
Outputs
Comm.
Ports
1763-L16AWA
120/240V ac
(10) 120V ac
(2) voltage input
0...10V dc
(6) relay
All individually
isolated
(1) RS-232/485
combo
(isolated)
(1) Ethernet
1763-L16BWA
120/240V ac
(6) 24V dc
(4) high-speed
24V dc
(1)
(1)
The 4 high-speed inputs (inputs 0 through 3) can be used for pulse latching or higher speed counting. Refer to Input
Specifications on page 24 and the MicroLogix 1100 Instruction Set Reference Manual, publication 1763-RM001, for more
information.
(2) voltage input
0 ...10V dc
(6) relay
All individually
isolated
(1) RS-232/485
combo
(isolated)
(1) Ethernet
1763-L16BBB
24V dc
(6) 24V dc
(4) high-speed
24V dc
(2) voltage input
0...10V dc
(2) relay (isolated)
(2) 24V dc FET
(2) high-speed
24V dc FET
(1) RS-232/485
combo
(isolated)
(1) Ethernet
1763-L16DWD
12/24V dc
(6) 12/24V dc
(4) high-speed
12/24V dc
(2) voltage input
0...10V dc
(6) relay
All individually
isolated
(1) RS-232/485
combo
(isolated)
(1) Ethernet
WARNING
EXPLOSION HAZARD
• Substitution of components may impair suitability for Class I, Division 2.
• Do not replace components or disconnect equipment unless power has been
switched off.
• Do not connect or disconnect components unless power has been switched off.
• This product must be installed in an enclosure. All cables connected to the
product must remain in the enclosure or be protected by conduit or other means.
• All wiring must comply with N.E.C. article 501-10(b).