Rockwell Automation 1763-L16xxx MicroLogix 1100 Programmable Controllers Installation Instructions User Manual
Page 30
30
Publication 1763-IN001B-EN-P - September 2007
Working Voltage (1763-L16BWA)
Description
1763-L16BWA
Power Supply Input to
Backplane Isolation
Verified by one of the following dielectric tests:1836V ac for 1 second or 2596V
dc for 1 second
265V ac Working Voltage (IEC Class 2 reinforced insulation)
Input Group to Backplane
Isolation and Input Group to
Input Group Isolation
Verified by one of the following dielectric tests: 1100V ac for 1 second or
1697V dc for 1 second
75V dc Working Voltage (IEC Class 2 reinforced insulation)
Output Group to Backplane
Isolation
Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second
265V ac Working Voltage (IEC Class 2 reinforced insulation).
Output Group to Output
Group Isolation
Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second
265V ac Working Voltage (basic insulation) 150V Working Voltage (IEC Class 2
reinforced insulation)
Working Voltage (1763-L16BBB)
Description
1763-L16BBB
Input Group to Backplane
Isolation and Input Group to
Input Group Isolation
Verified by one of the following dielectric tests: 1100V ac for 1 second or
1697V dc for 1 second
75V dc Working Voltage (IEC Class 2 reinforced insulation)
FET Output Group to
Backplane Isolation
Verified by one of the following dielectric tests: 1100V ac for 1 second or
1697V dc for 1 second
75V dc Working Voltage (IEC Class 2 reinforced insulation)
Relay Output Group to
Backplane Isolation
Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second
265V ac Working Voltage (IEC Class 2 reinforced insulation)
Relay Output Group to Relay
Output Group and FET
Output Group Isolation
Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second
265V ac Working Voltage (basic insulation), 150V Working Voltage
(IEC Class 2 reinforced insulation)