Mount the I/O Base
Mount the I/O base on a wall or panel, use the screw holes provided
in the adapter.
Mounting illustration for the ArmorPOINT I/O adapter
with I/O bases
IMPORTANT
The ArmorPOINT I/O module must be mounted on a grounded metal
mounting plate or other conductive surface.
ATTENTION
To comply with the CE Low Voltage Directive (LVD), all connected I/O must be
powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
ATTENTION
This product is intended to be mounted to a well-grounded mounting surface
such as a metal panel. Additional grounding connections from the power
supply mounting tabs or DIN rail (if used) are not required unless the mounting
surface cannot be grounded. Refer to Industrial Automation Wiring and
Grounding Guidelines, Rockwell Automation publication
additional information.