8 Logix5553 Controller

Publication 1756-IN017A-EN-P - August 2000

2. Attach the battery label:

a. Write on the battery label the date you install the battery.

b. Attach the label to the inside of the controller door.

ATTENTION

!

ATTENTION

!

To prevent possible battery leakage, you must replace a
battery, even if it is still good, according to the following
schedule:

ATTENTION

!

ATTENTION

!

Store batteries in a cool, dry environment. We recommend 25

°

C

with 40% to 60% relative humidity. You may store batteries for
up to 30 days between -45

°

to 85

°

C, such as during

transportation. To avoid possible leakage, do not store batteries
above 60

°

C for more than 30 days.

41025

battery label

If the rack inlet temperature is:

Replace the battery within:

0

°

to 35

°

C

No required replacement

36

°

to 40

°

C

3 years

41

°

to 45

°

C

2 years

46

°

to 50

°

C

16 months

51

°

to 55

°

C

11 months

56

°

to 60

°

C

8 months