Interpret the controller LEDs

Indicator:

Color:

Description:

RUN

off

The controller is in Program or Test mode.

green

The controller is in Run mode.

I/O

off

Either:

There are

no devices in the I/O

configuration of the controller.

The controller does

not contain a

project (controller memory is
empty).

green

The controller is communicating with all the
devices in its I/O configuration.

green flashing

One or more devices in the I/O configuration
of the controller are

not responding.

red flashing

The chassis is bad. Replace the chassis.

RS232

off

There is no activity.

green flashing

Data is being received or transmitted.

BAT

off

The battery will support memory.

red

The battery is

not present or may not support

memory. Replace the battery.

OK

off

No power is applied.

red flashing

Recoverable fault

red

Non-recoverable fault. To correct:

1. Cycle the chassis power.
2. Download the project.
3. Place the controller in Run mode.

If the problem continues to occur, contact
your Rockwell Automation representative or
local distributor.

green

The controller is OK.