Rockwell Automation 1738-IE4CM12 ArmorPoint 4-Channel 24V dc Analog Input Modules, Series A User Manual
Page 15

ArmorPoint 4-Channel 24V dc Analog Input Module, Series A 15
Publication
1738-IN024C-EN-P - March 2010
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50g
Emissions
CISPR 11: Group 1, Class A
ESD immunity
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80%AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100%AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz
3V/m with 1 kHz sine-wave 80%AM from 2000…2700 MHz
EFT/B immunity
IEC 61000-4-4:
±3 kV at 5 kHz on signal ports
Surge transient
immunity
IEC 61000-4-5:
±1 kV line-line (DM) on signal ports
±2 kV line-earth (CM) on signal ports
Conducted RF immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz
Certifications
Certification (when
product is marked)
(1)
Value
CE
European Union 2004/108/EC EMC Directive, compliant with:
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR11; Industrial Emissions
(1)
See the Product Certification link at
and other certification details.
Environmental (Continued)
Attribute Value