Specifications – Rockwell Automation 1757-FIM ProcessLogix Fieldbus Interface Module (FIM) Installation Instructions User Manual
Page 8
8 ProcessLogix Fieldbus Interface Module (FIM)
Publication 1757-IN913A-EN-P - October 2001
Specifications
FIM Specifications
Physical Interface
H1 FOUNDATION Fieldbus
Number of H1 Networks per FIM
1
(Each network defined as
a F
OUNDATION
Fieldbus 31.25 kbps H1 network)
2
Maximum Number of Fieldbus Devices per H1 Network
30
2
Maximum Number of FIMs per 1757-PLX52 Controller
(Each FIM counts as 3 IOMs in the IOMs/CPM
calculation.)
21
Maximum Number of Fieldbus Devices per 1757-PLX52
Controller
Maximum Number of FIMs per Server (Redundant or
Non-Redundant)
100
Maximum Number of H1 Networks per Server (Redundant
or Non-Redundant)
200
Maximum Number of Fieldbus Devices per Server
3000
Maximum Single-Variable Publications per Second on an
H1 network
15
Maximum number of VCRs (Virtual Communications
Relationships) per Network
64
3
Electro-static Discharge
IEC 1000-4-2: 1995
Operating Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal
Shock):
0 to 60°C (32 to 140°F)
Storage Temperature
IEC 60068-2-1 (Test Ab, Un-packaged
Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged
Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged
Non-operating Thermal Shock):
–40 to 85°C (–40 to 185°F)
Relative Humidity
IEC 60068-2-30 (Test Db, Un-packaged
Non-operating
Damp Heat):
5 to 95% non-condensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
0.5g @ 10-500Hz
Shock
IEC 60068-2-27: Test Ea (Unpackaged shock,
ES#002)
Operating 5g
Non-operating 20g