Communicate with your armorblock maxum module, Devicenet cable – Rockwell Automation 1792D-16BVTOD ArmorBlock MaXum 16 Input Module Series B User Manual
Page 7
ArmorBlock MaXum 16 Input Module Series B 7
Publication 1792D-IN016B-EN-P - September 2000
DeviceNet Cable
DeviceNet cables are described in the installation publications for the
cable base of your choice. Refer to the following publications:
•
1792D-IN009B-EN-P ArmorBlock MaXum Cable Base
Installation Guide
•
DN-6.7.2 DeviceNet Cable Planning and Installation Manual
Communicate With Your ArmorBlock MaXum Module
This ArmorBlock module’s I/O is exchanged with the master through
a polled, change-of-state, or cyclic connection.
The module consumes and produces input data as follows:
Cyclic - allows configuration of the block as an I/O client. The block
will produce its I/O cyclically at the rate configured.
Polled - a master initiates communication by sending its polled I/O
message to the module. The 16 input module scans the inputs and
fault bits producing a response that reflects their status.
Change of State - productions occur when an input changes or a
fault condition occurs. If no input or fault condition change occurs
within the expected packet rate, a heartbeat production occurs. This
heartbeat production tells the scanner module that the module is alive
and ready to communicate.
Refer to the table below for the word/bit definitions.
Type of I/O Connections
Consumes
Produces
Cyclic
0 Byte
4 Bytes
Polled
0 Byte
4 Bytes
Change-of-State
0 Byte
4 Bytes
Bit
07
06
05
04
03
02
01
00
Produces 0
I7
I6
I5
I4
I3
I2
I1
I0
Produces 1
I15
I14
I13
I12
I11
I10
I9
I8
Produces 2
ISC-H
ISC-G
ISC-F
ISC-E
ISC-D
ISC-C
ISC-B
ISC-A
Produces 3
OW-H
OW-G
OW-F
OW-E
OW-D
OW-C
OW-B
OW-A
Where: OW = Off Wire I = Input ISC = Input Short Circuit in Sensor Source Voltage