Specifications – Rockwell Automation 1792D-16BVTOD ArmorBlock MaXum 16 Input Module Series B User Manual
Page 11
ArmorBlock MaXum 16 Input Module Series B 11
Publication 1792D-IN016B-EN-P - September 2000
Specifications
16 Input Module - Cat. No. 1792D-16BVTOD
Input Specifications
Max.
Min.
Inputs per block
16 - 3 wire or dry contact PNP or NPN devices or 8 -
4 wire PNP or NPN devices
Sensor Source Current (per input)
See graphic below.
On-state Voltage
25V dc
10V dc
On-state Current
10mA
2mA
Off-state Voltage
5V dc
-
Off-state Current
-
1.5mA
Off-Wire Sense Current
0.5mA
-
General Specifications
Indicators
Net/Mod Status - red/green
Logic Status - red/green
Point LED - yellow/orange/red
Communication Rate
•
125Kbps @ 500 meters(1600 feet) for thick cable,
flat media length 375 meters
•
250Kbps @ 200 meters(600 feet) for thick cable,
flat media length 150 meters
•
500Kbps @ 100 meters (330 feet) for thick cable,
flat media length 75 meters
DeviceNet Power Voltage
Current
Refer to the graphs in the
Overview section of the
ArmorBlock I/O Family Technical
Data, pub. no.
1792-TD001B-EN-P.
25V dc max
200mA max (no sensors)
11V dc min up to
1.6A (16 sensors
@50mA per sensor)
Dimensions (assembled to base)
inches - (Millimeters)
1.9H x 2.7w x6.85D
(48.26)H x (68.6)W x (174)D
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration
-25 to 60
o
(-13 to 140
o
F)
-25 to 80
o
C (-13 to 176
O
F)
Up to 100%
30g peak acceleration, 11 (+1) ms pulse width
50g peak acceleration, 11(+1)ms pulse width
Tested 10g @ 10-500Hz per IEC 68-2-6
Conductors
Publication DN-6.7.2
Enclosure
Meets or exceeds IP67
Agency Certification
(when product is marked)
CSA certified
CSA Class 1, Division 2, Groups A, B, C, D certified
UL listed
CE marked for all applicable directives