Specifications – Rockwell Automation 1788-DNBO DeviceNet Daughtercard Installation Instructions User Manual
Page 15
DeviceNet Daughtercard 15
Publication 1788-IN053A-EN-P - December 2001
Specifications
Characteristic
Value
Power Requirements
Host
DeviceNet
5V dc @ 260mA
(1)
24V dc @ 20mA Class 2
Power Consumption
Thermal Dissipation
5 V dc, 1.3W
24 V dc, 0.48W.
Total=1.78W
6.1 BTU/hr
Isolation Voltage
Tested to withstand 707 V dc for 60 seconds
RTB Screw Torque
5-7 inch-pounds (0.56-0.8 Nm)
Conductors Wire Size
Category
24-12 AWG (0.205-3.31 mm
2
) stranded copper
(2)
3/64 inch (1.2mm) insulation maximum
2
Emissions
CISPR 11: Group 1, Class A (with appropriate enclosure)
ESD Immunity
IEC 61000-4-2:
6kV contact discharges
8kV air discharges
Radiated RF Immunity
IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz
EFT/B Immunity
IEC 61000-4-4:
±2kV at 5kHz on communications ports
Surge Transient Immunity
IEC 61000-4-5:
+2kV line-earth (CM) on shielded ports
Conducted RF Immunity
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz
Enclosure Type Rating
None (open-style)
Operating Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
This product is suitable for application in equipment that is rated 0 to 60
o
C
(32 to 140
o
F) maximum. It is acceptable for the ambient slot temperature
immediately surrounding this
product to reach 85
o
C (185
o
F) maximum.
Storage Temperature
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
–40 to 85°C (–40 to 185°F)
Relative Humidity
IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
5 to 95% non-condensing
Shock
IEC60068-2-27 (Test Ea, Unpackaged Shock):
Operating 30g
Non-operating 50g