6 Compact™ Solid State 24V dc Source, High Current Output Module

Publication 1769-IN063A-EN-P - March 2003

5. Push the bus lever back slightly to clear the positioning tab (3). Use your

fingers or a small screw driver.

6. To allow communication between the controller and module, move the bus

lever fully to the left (4) until it clicks. Ensure it is locked firmly in place.

7. Attach an end cap terminator (5) to the last module in the system by using

the tongue-and-groove slots as before.

8. Lock the end cap bus terminator (6).

Mounting Compact I/O Modules

Minimum Spacing

Maintain spacing from
enclosure walls,
wireways, adjacent
equipment, etc. Allow 50
mm (2 in.) of space on all
sides for adequate
ventilation, as shown:

ATTENTION

!

When attaching I/O modules, it is very important that the bus
connectors are securely locked together to ensure proper
electrical connection.

IMPORTANT

A 1769-ECR or 1769-ECL right or left end cap must be used to terminate the
end of the serial communication bus.

ATTENTION

!

During panel or DIN rail mounting of all devices, be sure that all debris
(metal chips, wire strands, etc.) is kept from falling into the module. Debris
that falls into the module could cause damage on power up.

Top

Bottom

Side

Side

Compac

t I

/O

Compac

t I

/O

Compac

t I

/O

Compac

t I

/O

Compac

t I

/O

End Cap

Host Controller