2. Route the wire under the terminal pressure plate. You can use the bare wire
or a spade lug. The terminals will accept a 6.35 mm (0.25 in.) spade lug.
3. Tighten the terminal screw making sure the pressure plate secures the wire.
Recommended torque when tightening terminal screws is 0.68 Nm (6 in-lbs).
Simplified Output Circuit Diagram
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires with the following restrictions:
TIP
The terminal screws are non-captive. Therefore, it is
possible to use a ring lug [maximum 1/4 inch o.d. with
a 0.139 inch minimum i.d. (M3.5)} with the module.
TIP
If you need to remove the finger-safe cover, insert a
screw driver into one of the square, wiring holes and
gently pry the cover off. If you wire the terminal block
with the finger-safe cover removed, you will not be
able to put it back on the terminal block because the
wires will be in the way.
Wire Type
Wire Size
Terminal Screw
Torque
Retaining Screw
Torque
Solid
Cu-90°C (194°F)
#14 to #22 AWG
0.68 Nm (6 in-lbs)
0.46 Nm (4.1 in-lbs)
Stranded
Cu-90°C (194°F)
#16 to #22 AWG
0.68 Nm (6 in-lbs)
0.46 Nm (4.1 in-lbs)
VCC
ASIC
VDC
OUT
COM
Logic Side
User Side