Rockwell Automation 1769-OV32T Compact Module User Manual
Page 7

Compact 32-point Solid-state 24V dc Sink Output Module 7
Publication 1769-IN073B-EN-P - September 2005
Panel Mounting Using the Dimensional Template
Locate holes every 17.5 mm (0.689 in.) to allow for a mix of single-wide and
one-and-a-half-wide modules (e.g. 1769-OA16).
Panel Mounting Procedure Using Modules as a Template
The following procedure allows you to use the assembled modules as a template for drilling
holes in the panel. If you have sophisticated panel mounting equipment, you can use the
dimensional template provided on page 7. Due to module mounting hole tolerance, it is
important to follow these procedures:
1. On a clean work surface, assemble no more than three modules.
2. Using the assembled modules as a template, carefully mark the center of all
module-mounting holes on the panel.
3. Return the assembled modules to the clean work surface, including any previously
mounted modules.
4. Drill and tap the mounting holes for the recommended M4 or #8 screw.
5. Place the modules back on the panel, and check for proper hole alignment.
6. Attach the modules to the panel using the mounting screws.
7. Repeat steps 1 to 6 for any remaining modules.
TIP
If mounting more modules, mount only the last one of this
group and put the others aside. This reduces remounting time
during drilling and tapping of the next group.
Host Contro
ller
Spacing for single-wide modules 35 mm (1.378 in.)
Refer to host controller documentation for this dimension.
Note: Overall hole spacing
tolerance: ±0.4 mm (0.016 in.).
Spacing for one-and-a half-wide modules 52.5 mm (2.067 in.)