Controlnet discrete input objects, Alarm handling for discrete inputs – Rockwell Automation 1788-CN2FF ControlNet-to-FOUNDATION Fieldbus H1 Linking Device User Manual User Manual
Page 36
1788-6.5.1 - January 1999
4-10
Using the ControlNet-to-FOUNDATION Fieldbus H1 Linking Device
ControlNet Discrete Input Objects
The linking device creates an instance of a ControlNet DI object for every
wired channel in the MDI block instances. Each instance of the ControlNet
DI object has the attributes and access rules shown in Table 4.C.
All attributes in Table 4.C are created if a standard Fieldbus DI function
block is connected to a channel on an MDI block. Otherwise, DiscAlmFlag
is not created.
Alarm Handling for Discrete Inputs
You can configure Fieldbus DI function blocks to detect and report alarms.
The process alarm (DISC_ALM) are exposed through the ControlNet DI
object. When you connect a DI function block to an MDI block, the
NI-FBUS Configurator configures the field device to send the alarm to the
linking device.
In Fieldbus terminology, confirming an alarm means that the alarm has been
received by an operator, and acknowledging an alarm means that the
operator has taken the necessary action.
When an alarm condition is detected by a Fieldbus function block, the alarm
is said to be ACTIVE. An active alarm should be Acknowledged and
Confirmed after the condition causing the alarm is corrected. When the
function block detects the alarm condition is no longer present, the alarm is
said to be CLEARED. The CLEARED state must be Confirmed when it is
detected. Users of the LD use the alarm attributes to process Fieldbus
alarms.
Each attribute corresponding to a process alarm has the three alarm-related
bits as shown in Figure 4.8.
Table 4.C ControlNet Discrete Input Object Attributes
Attribute
Number
Name
Type
Access
Initial Value
Remarks
3
Value
Boolean
Get
0
4
CNStatus
Boolean
Get
Bad
ControlNet status. 0-Good; 1-Bad.
150
Ffstatus
uint8
Get
Bad:Out of Service
Fieldbus status of the value; obtained from
the Fieldbus device.
151
TagDesc
String
Get
As configured
Tag of the Fieldbus function block that is
represented by this object instance.
156
DiscAlmFlag
uint8
Get/Set
0
See Alarm Handling for Discrete Inputs