Input delay times – Rockwell Automation 1793-IB2XOB2PS FLEX INTEGRA 2 INPUT/2 PROTECTED OUTPUT MODUL User Manual
Page 6

6
FLEX Integra 2 Input/2 Protected Output Module
Publication 1793-5.3 - September 1999
Memory Mapping
Setting the Input Delay Time
You can select the input delay time (DT) for input channels 00 and 01.
Select the input delay time by setting the corresponding bits in the
configuration word (word 3) for the module.
For example, to set a delay time of 4ms for an input module at address rack
1, module group 0, set bits 02, 01 and 00 as shown below.
Input Delay Times
Bit/
Word
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Read
Reserved
I1
I0
Write
Reserved
O1
O0
Write
Reserved
FT time
Where: I = Input
O = Output
FT = Filter time
02
01
00
Filter Time for Inputs 00-01
Selected
Filter Time
0
0
0
Filter Time 0 (default)
512
μs
0
0
1
Filter Time 1
1ms
0
1
0
Filter Time 2
2ms
0
1
1
Filter Time 3
4ms
1
0
0
Filter Time 4
8ms
1
0
1
Filter Time 5
16ms
1
1
0
Filter Time 6
32ms
1
1
1
Filter Time 7
64ms