Maximum input data format (base modules -4b4p) – Rockwell Automation 1791R-XXXX CompactBlock Distributed I/O on Remote I/O Series D I.I. User Manual
Page 30
![background image](/manuals/579670/30/background.png)
30 CompactBlock Distributed I/O on Remote I/O Series D
Publication
1791R-IN002B-EN-P - August 2003
Maximum Output Data Format (Base Modules -8B8P or --8V8P)
Word
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
Reserved
O7
O6
O5
O4
O3
O2
O1
O0
Base
1
Reserved
Analog Output Data Channel 0
2
Reserved
Analog Output Data Channel 1
3
OE
HLS
R
IF
IR3
IR2
IR1
IR0
IM3 IM2 IM1 IM0 OR1 OR0 OM1 OM0
4
Reserved
5
Reserved
OM x Output Mode Selection
Set “0”: Voltage Mode
Set “1”: Current Mode
OR x Output Range Selection on Current ModeSet “0”: 4-20mA
Set “1”: 0-20mA
IM x Input Channel Mode Select
Set “0”: Voltage Mode
Set “1”: Current Mode
IR x Input Range Select on Current Mode
Set “0”: 4-20mA
Set “1”: 0-20mA
IF
Input Filter Selection
Set “0”: 50Hz
Set “1”: 60Hz
R Reserved;
HLS HLS/OFF
Set “0”: Output Reset
Set “1”: Hold Last State
OE
Output Enable
Set “0”: Output Disabled
Set “1”: Output Enabled
(Output is 0mA at 0-20mA mode and 4-20mA mode
and 0V at 0-10V mode when this bit is 0)
Maximum Input Data Format (Base Modules -4B4P)
Bit Position
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
Reserved
In3
In2
In1
In0
Base
1
Reserved
Analog Input Data Channel 0
2
Reserved
Analog Input Data Channel 1
3
Reserved
Analog Input Data Channel 2
4
Reserved
Analog Input Data Channel 3
5
URo1 URo0 ORo1 ORo0 OW3 OW2 OW1 OW0 ORi3 ORi2 ORi1 ORi0 Reserved
RF
UF
UF
Module Unrecoverable Fault
Set “0”: No Error
Set “1”: Error
RF Module
Recoverable
Fault
Set
“0”: No Error
Set “1”: Error
ORi x Over Range Input Channel
Set “0”: No Over Range
Set “1”: Over Range
OW x Input Open Wire (@ 4-20mA Range)
Set “0”: No Open Wire
Set “1”: Open Wire
ORo x Output Data Over Range
Set “0”: No Over Range
Set “1”: Over Range
URo x Output Data Under Range (@4-20MA Range)Set “0”: No Under RangeSet “1”: Under Range