12 1738 ArmorPOINT I/O EtherNet/IP Adapter
Publication 1738-IN031A-EN-P - July 2013
Network
Activity
Off
No link established.
Flashing
green/Off
Transmit or receive activity present.
Solid green
Link established.
Network
Status
Off
Device not initialized. The module does not have an IP address.
Flashing
green
No CIP connections present. Device has an IP address, but no CIP
connections are established.
Solid green
CIP connections present. Device online and has an IP address, and CIP
connections are established.
Flashing red
One or more CIP connections in timed-out state. Check for I/O module failure
and controller operation.
Solid red
Duplicate IP address detected.
Verify IP address setting and correct, as needed.
Flashing
red/green
The module is performing a self-test (only occurs during cycle
power test).
POINTBus
Status
Off
Device not powered – check module status indicator.
Flashing
red/green
LED cycle power test present.
Flashing red
Recoverable fault occurred:
• At cycle power, the number of expected modules does not equal the
number of modules present.
• A module is missing.
• Node fault (I/O connection timeout) occurred.
Solid red
Unrecoverable fault occurred – the adapter is bus off.
Flashing
green
Firmware (NVS) update in progress.
Solid green
Adapter online with connections established (normal operation,
Run mode).
System
power
Off
Not active; field power is off or DC-DC converter problem present.
Solid green
System power is on; DC-DC converter is active (5V).
Adapter
power
Off
Not active; field power is off.
Solid green
Power is on; 24V is present.
Indicator Status for Modules
Indicator State
Description