Specifications, Derating curve – Rockwell Automation 1794-IT8_IR8 FLEX I/O 8 Thermocouple Input Module User Manual
Page 5
5
Publication 1794-IN021D-EN-P - August 2003
Specifications
Derating Curve
Specifications
1794-IT8
1794-IR8
Number of Inputs
8 channels
Module Location
Cat. No. 1794-TB2, -TB3, -TB3S, -TB3T and -TB3TS Terminal Base Units
Nominal Input
Ranges
-76.5 to +76.5mV
1 to 433 ohms
Supported
Thermocouple Types
(1794-IT8 only)
Type
Range °C
Range °F
B
300 to 1800°C
(572 to 3272°F)
C
0 to 2315°C
(32 to 4199°F)
E
-270 to 1000°C
(-454 to 1832°F)
J
-210 to 1200°C
(-346 to 2192°F)
K
-270 to 1372°C
(-454 to 2502°F)
TXK/XK(L)
-200 to 800°C
(-328 to 1472°F)
N
-270 to 1300°C
(-454 to 2372°F)
R
-50 to 1768°C
(-58 to 3214°F)
S
-50 to 1768°C
(-58 to 3214°F)
T
-270 to 400°C
(-454 to 752°F)
Supported RTDs
(1794-IR8 only)
Resistance
100
Ω
Pt
α
= 0.00385 Euro (-200 to +870°C)
100
Ω
Pt
α
= 0.003916 U.S. (-200 to +630°C)
200
Ω
Pt
α
= 0.00385 Euro (-200 to +400°C)
500
Ω
Pt
α
= 0.00385 Euro (-200 to +630°C)
100
Ω
Nickel
α
= 0.00618 (-60 to +250°C)
120
Ω
Nickel
α
= 0.00672 (-60 to +250°C)
200
Ω
Nickel
α
= 0.00618 (-60 to +250°C)
500
Ω
Nickel
α
= 0.00618 (-60 to +250°C)
10
Ω
Copper
α
= 0.00427 (-200 to +260°C)
RTD Excitation
Current
718.36
μ
A
Resolution
16 bits (2.384
μ
V typical)
16 bits across 435 ohms
Accuracy
Refer to “Calculating the Accuracy”
section in Appendix A of the user
manual (1794-UM007)
Without calibration, at low humidity:
Normal mode: 0.05% full scale (max)
Enh. mode: 0.01% full scale (typical)
Common Mode
Rejection
-115db @ 60Hz; -100db @ 50Hz
-120db @ 60Hz; -100db @ 50Hz with
A/D filter cutoff @ 10Hz
Common Mode Input
Range
+10V maximum
0V between channels (common
return)
Isolation Voltage
Tested at 850V dc for 1s from inputs and user power to logic side
Data Format
16-bit 2’s complement or offset binary (unipolar)
Normal Mode Noise
Rejection
-60db @ 60Hz
-60db @ 60Hz for A/D filter cutoff @
10Hz
Input Offset Drift
w/Temperature
+6mV/°C maximum
1.5 milliohm/°C maximum
Gain Drift w/Temp.
10ppm/°C maximum
Normal mode: 20ppm/°C max.
Enhanced mode: 10ppm/°C max.
Channel Bandwidth
0-2.62Hz (-3db)
Settling time to 100%
of final value
Available at system throughput rate
System Throughput
325ms (1 channel scanned),
programmable to 28ms
2.6s (8 channels scanned),
programmable to 224ms
Normal mode - 325ms (1 channel
scanned), programmable to 28ms
2.6s (8 channels scanned),
programmable to 224ms
Enhanced mode - programmable
from 56 to 650ms/channel - 650ms
(1 channel scanned), 2.925s (8
channels scanned)
Open TC/RTD Circuit
Detection
Out of range reading (upscale)
Open TC/RTD
Detection Time
Available at system throughput rate
Overvoltage
Capability
35V dc, 25V ac continuous at 25°C
Overall Drift with
Temperature
50ppm/°C of span (maximum)
Cold Junction
Compensation
Range: 0 to 70°C
A-B catalog number 1794-CJC2
Channel to channel
isolation
+10V
0V
Indicators
1 red/green power status indicator
Flexbus Current
20mA
Power Dissipation
3.0W maximum @ 31.2V dc
Thermal Dissipation
Maximum 10.2 BTU/hr @ 31.2V dc
Keyswitch Position
3
General Specifications
External dc Power
Supply
Voltage Range
Supply Current
24V dc nominal
19.2 to 31.2V dc (includes 5% ac ripple)
19.2 to 31.2V dc for ambient temperatures < 40°C
24V dc maximum for ambient temperatures = 55°C
See derating curve
150mA @ 24V dc
Dimensions (with
module installed)
31.8H x 3.7W x 2.1D inches
45.7H x 94W x 53.3D mm
Environmental Conditions
Operating
Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 55°C (32 to 131°F)
Storage
Temperature
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
–40 to 85°C (–40 to 185°F)
Relative Humidity
IEC 60068-2-30 (Test Db, Un-packaged Non-operating
Damp Heat):
5 to 95% non-condensing
Vibration
IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz
Shock
IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g
Emissions
CISPR 11:
Group 1, Class A (with appropriate enclosure)
ESD Immunity
IEC 61000-4-2:
4kV contact discharges
8kV air discharges
Radiated RF
Immunity
IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz
EFT/B Immunity
IEC 61000-4-4:
±2kV at 5kHz on signal ports
Surge Transient
Immunity
IEC 61000-4-5:
+2kV line-earth(CM) on shielded ports
Conducted RF
Immunity
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 30MHz
Enclosure Type Rating
None (open-style)
Signal Conductors
Thermocouple
Millivolt
Category
2
Thermocouple - Use appropriate
shielded thermocouple wire
1
Belden 8761
2
2-wire -Belden 9501
3-wire, less than 100ft with normal
humidity - Belden 9533
3-wire, greater than 100ft or normal
humidity (>55°C for > 8 hrs) - Belden
83503
Power Conductors
Wire Size
Category
2
12AWG (4mm
2
) stranded copper wire rated at 75°C or higher
3/64 inch (1.2mm) insulation maximum
2
Certifications (when
product is marked)
3
UL
UL Listed Industrial Control Equipment
C
-UL-
US
UL Listed Industrial Control Equipment, certified for US and Canada
(1794-IT8)
C
-UL-
US
UL listed for Class I, Division 2, Groups A, B, C and D Hazardous
locations, certified for US and Canada (1794-IT8)
CSA
CSA certified Process Control Equipment
CSA
CSA certified for Class I, Division 2, Groups A, B, C and D
Hazardous locations
EEx
3
European Union 94/9/EEC ATEX Directive, compliant with:
EN 50021; Potentially Explosive Atmospheres,
Protection “n” (Zone 2)
CE
3
European Union 89/336/EEC EMC Directive,
compliant with:
EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
C-Tick
3
Australian Radiocommunications Act compliant with
AS/NZS CISPR 11, Industrial Emissions
1
Refer to thermocouple manufacturer for proper thermocouple extension.
2
You use this category information for planning conductor routing as described in Allen-Bradley
publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines.
3
For the latest up-to-date information, see the Product Certification link at www.ab.com for Declarations of
Conformity, Certificates and other certification details. For notification of any additional release notes, refer to
www.ab.com/manuals/.
19.2
24.0
31.2
Safe operating area
The area within the curve represents the safe operating range for the module
under various conditions of user supplied 24V dc supply voltages and ambient
temperatures.
0˚C
25˚C
40˚C
50˚C 55˚C
User Applied 24V dc Supply
Ambient Temperature