Block transfer read and write – Rockwell Automation 1794-IT8_IR8 FLEX I/O 8 Thermocouple Input Module User Manual
Page 4
4
Publication 1794-IN021D-EN-P - August 2003
Block Transfer Read and Write
The following block transfer read and write word bit information is presented
for experienced users only. Refer to the user manuals (publication
1794-UM004 for the RTD or 1794-UM007 for TC/mV) for these products for
complete information on programming and configuring your modules.
Input Map (Read) for 1794-IR8 and 1794-IT8
Temperature and resistance data is returned with an implied decimal point. For
example, a temperature data of 1779 is 177.9°. Resistance data of 2034 is
203.4
Ω.
mV data is returned with an implied decimal point of 2 decimal points.
for example, 7500 is 75mV.
Output Map (Write) for 1794-IR8 and 1794-IT8
Data Format for All Channels - Write Word 0
RTD Type - Write Word 1 and 2
Thermocouple Type - Write Word 1 and 2
Dec.
15
14
13
12
11
10
9
0
7
6
5
4
3
2
1
0
Oct.
17
16
15
14
13
12
11
10
7
6
5
4
3
2
1
0
Word
0
Reserved
1
Channel 0 Input Data
2
Channel 1 Input Data
3
Channel 2 Input Data
4
Channel 3 Input Data
5
Channel 4 Input Data
6
Channel 5 Input Data
7
Channel 6 Input Data
8
Channel 7 Input Data
9
Overrange Alarm Bits (channel 0 = bit 8, etc.)
Underrange Alarm Bits (channel 0 = bit 0, etc.
10
(-IT8)
0
0
0
0
0
Bad
Cal
Cal
Done
Cal
Rng
0
Diag.
Status Bits
Pwr
Up
Bad
Struct
CJC
Over
CJC
Under
10
(-IR8)
0
0
0
0
0
Bad
Cal
Cal
Done
Cal
Rng
RI
UP
Critical
Error Bits
Pwr
Up
Res.
0
0
Dec.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Oct.
17
16
15
14
13
12
11
10
7
6
5
4
3
2
1
0
IT8
Word 0
8-Bit Calibration Mask
Cal
Clk
Cal
Hi/
Lo
Filter Cutoff
FDF
MDT
IR8
Word 0
8-Bit Calibration Mask
Cal
Clk
Cal
Hi/
Lo
Filter Cutoff
Enh
MDT
Word 1
Thermocouple or RTD
Type Ch 3
Thermocouple or RTD
Type Ch 2
Thermocouple or RTD
Type Ch 1
Thermocouple or RTD
Type Ch 0
Word 2
Thermocouple or RTD
Type Ch 7
Thermocouple or RTD
Type Ch 6
Thermocouple or RTD
Type Ch 5
Thermocouple or RTD
Type Ch 4
Word 3
Reserved
Where: FDF = Fixed digital filter (TC only)
Enh = Enhanced mode (RTD only)
MDT = Module Data Type
Bit
01
00
0
0
°C
0
1
°F
1
0
Bipolar counts scaled between -32767 to +32767
1
1
Unipolar counts scaled between 0 and 65535
0101 thru 1111 not used
RTD Type
Bit
03
02
01
00
Channel 0 (Write word 1)
Bit
07
06
05
04
Channel 1 (Write word 1)
Bit
11
10
09
08
Channel 2 (Write word 1)
Bit
15
14
13
12
Channel 3 (Write word 1)
Bit
03
02
01
00
Channel 4 (Write word 2)
Bit
07
06
05
04
Channel 5 (Write word 2)
Bit
11
10
09
08
Channel 6 (Write word 2)
Bit
15
14
13
12
Channel 7 (Write word 2)
0
0
0
0
Resistance (default = mV)
0
0
0
1
No sensor connected - do not scan
0
0
1
0
100
Ω
Pt
α
= 0.00385 Euro (-200 to +870°C)
0
0
1
1
100
Ω
Pt
α
= 0.003916 U.S. (-200 to +630°C)
0
1
0
0
200
Ω
Pt
α
= 0.00385 Euro (-200 to +630°C)
0
1
0
1
500
Ω
Pt
α
= 0.00385 Euro (-200 to +630°C)
0
1
1
0
Reserved
0
1
1
1
10
Ω
Copper (-200 to +260°C)
1
0
0
0
120
Ω
Nickel (-60 to +250°C)
1
0
0
1
100
Ω
Nickel (-60 to +250°C)
1
0
1
0
200
Ω
Nickel (-60 to +250°C)
1
0
1
1
500
Ω
Nickel (-60 to +250°C)
1
1
0
0
Reserved
Thermocouple Type
Range
Bit
03
02
01
00
Channel 0 (Write word 1)
Bit
07
06
05
04
Channel 1 (Write word 1)
Bit
11
10
09
08
Channel 2 (Write word 1)
Bit
15
14
13
12
Channel 3 (Write word 1)
Bit
03
02
01
00
Channel 4 (Write word 2)
Bit
07
06
05
04
Channel 5 (Write word 2)
Bit
11
10
09
08
Channel 6 (Write word 2)
Bit
15
14
13
12
Channel 7 (Write word 2)
0
0
0
0
mV (default)
0
0
0
1
B
300 to 1800°C
(572 to 3272°F)
0
0
1
0
E
-270 to 1000°C
(-454 to 1832°F)
0
0
1
1
J
-210 to 1200°C
(-346 to 2192°F)
0
1
0
0
K
-270 to 1372°C
(-454 to 2502°F)
0
1
0
1
R
-50 to 1768°C
(-58 to 3214°F)
0
1
1
0
S
-50 to 1768°C
(-58 to 3214°F)
0
1
1
1
T
-270 to 400°C
(-454 to 752°F)
1
0
0
0
C
0 to 2315°C
(32 to 4199°F)
1
0
0
1
N
-270 to 1300°C
(-450 to 2372°F)
1
0
1
0
TXK/XK(L)
-200 to 800°C
(-328 to 1472°F)
1
0
1
1
Reserved
1
1
0
0
Module reports cold junction sensor temperature for channels 00-03
1
1
0
1
Module reports cold junction sensor temperature for channels 04-07
1
1
1
0
Reserved
1
1
1
1
No input device connected - do not scan