beautypg.com

Rockwell Automation Logix5000 Controllers Function Block Diagram Programming Manual User Manual

Page 12

background image

Chapter 1 Program a Function Block Diagram

In this example, the value of tagA is stored at the beginning of the execution of the

routine. The stored value is used when Block_01 executes. The same stored value

is also used when Block_02 executes. If the value of tagA changes during execution

of the routine, the stored value of tagA in the IREF does not change until the next

execution of the routine.

This example is the same as the previous example. The value of tagA is stored only

once at the beginning of the execution of the routine. The routine uses this stored

value throughout the routine.

With version 11 and later of the application, use the same tag in multiple IREFs

and an OREF in the same routine. Because the values of tags in IREFs are latched

every scan through the routine, all IREFs use the same value, even if an OREF

obtains a different tag value during execution of the routine. In this example, if

tagA has a value of 25.4 when the routine starts executing this scan, and Block_01

changes the value of tagA to 50.9, the second IREF wired into Block_02 still uses a

value of 25.4 when Block_02 executes this scan.

12

Rockwell Automation Publication 1756-PM009E-EN-P - October 2014