Specifications - 1794-OV32 Flex I/O Digital Sinking Output Module

Specification

Description

Number of I/O channels

32 (2 groups of 16), nonisolated within groups, sinking

Module location

Cat. No. 1794-TB32, -TB32S

On-state voltage

10V dc minimum

24V dc nominal

31.2V dc maximum

Output current rating

14A maximum per module

6A total for channels 0...15

8A total for channels 16...31

Off-state voltage

31.2V dc maximum

On-state current

1.0mA minimum per channel

500mA maximum per channel

Surge current

2A for 50ms, repeatable every 2s

Off-state leakage

0.5mA maximum

On-state voltage drop

0.2V dc maximum

Isolation voltage

50V (continuous), Basic Insulation Type

Type tested at 707V dc for 60 s, between field side and system

No isolation between individual channels

Output signal delay

(1)

Off to On - 0.5ms maximum

On to Off - 1.0ms maximum

Flexbus current

110mA

Power dissipation

4.4W @ 31.2Vdc

Thermal dissipation

8.53 BTU/hr maximum @ 31.2V dc

Indicators (field side indication,
customer device driven)

32 yellow status indicators

Pilot Duty Rating

DC13

Fusing

Module outputs are not fused. Fusing is recommended. If fusing is desired,
you must provide external fusing. Use SAN-O MQ4-800 800mA fuses.

(1)

The time from the receipt of an on or off command to the output actually turning on or off.

General Specifications 1794-IV32, 1794-OV32

Specification

Description

Terminal base screw torque

Determined by installed terminal base

Dimensions (with module installed)

H x W x D

94 x 94 x 69 mm

3.7 x 3.7 x 2.7 inches

External dc power supply voltage

24V dc nominal

Voltage range

1794-IV32 - 19.2...31.2Vdc (including 5% ac ripple)

1794-OV32 - 10.0...31.2Vdc (including 5% ac ripple)

Supply current

1794-OV32 -50mA @ 24V dc

North American temp code

T4A

Keyswitch position

2

Enclosure type rating

None (open-style)

Wire size

Determined by installed terminal base

Wiring category

(1)

2- on signal ports

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1

.

Environmental Specifications

Specification

Description

Operating temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0...55 °C (32...131 °F)

Storage temperature

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):

-40...85 °C (-40...185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5...95% non-condensing

Vibration

IEC60068-2-6 (Test Fc, Operating):

5g @ 10...500Hz

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock):

Operating 30g

Non-operating 50g

Emissions

CISPR 11:

Group 1, Class A (with appropriate enclosure)

ESD immunity

IEC 61000-4-2:

6kV contact discharges

8kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz

1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:

±2k V at 5kHz on signal ports

Surge transient immunity

IEC 61000-4-5:

±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports

Conducted RF immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz

Certifications

Certifications

(when product is marked)

(1)

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada.

See UL File E65584.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,

certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

(1)

See the Product Certification link at

www.ab.com

for Declarations of Conformity, Certificates, and other certification

details.