20 POINT I/O 2 Port Ethernet Adapter

Publication

1734-IN040B-EN-P - December 2009

Specifications

POINT I/O Ethernet Adapter - 1734-AENTR

Attribute

Value

Expansion I/O capacity

• 63 modules max

• 5 rack optimized connections (for digital modules only)

max

• 20 direct connections max

• 1734-AENTR backplane current output = 0.8 A.

• Actual number of modules can vary.

• Add up current requirements of modules you want to

use to make sure they do not exceed the amperage
limit of 0.8 A for the 1734-AENTR adapter.

• Backplane current can be extended beyond 0.8 A by

using 1734-EP24DC backplane extension power
supplies.

• Add multiple 1734-EP24DC modules to reach the 63

module max.

POINTBus current
requirements

• 75 mA (Catalog numbers 1734-IB2, 1734-IB4,

1734-IB8, 1734-IV2, 1734-OB2, 1734-OB4, 1734-OB8,
1734-OB2E, 1734-OB2EP, 1734-OB4E, 1734-OB8E,
1734-OV2E, 1734-OV4E, 1734-IE2C, 1734-OE2C,
1734-IE2V, 1734-OE2V, 1734-IA2, 1734-IM2,
1734-OA2, 1734-232ASC, 1734-485ASC)

• 80 mA (Catalog number 1734-OW2)

• 100 mA (Catalog number 1734-OX2)

• 110 mA (Catalog number 1734-SSI)

• 160 mA (Catalog number 1734-IJ2)

• 175 mA (Catalog number 1734-IT2I)

• 180 mA (Catalog number 1734-VHSC5, 1734-VHSC24)

• 220 mA (Catalog number 1734-IR2)

Module location

Starter module - left side of the 1734 system