POINT I/O 2 Port Ethernet Adapter 13

Publication

1734-IN040B-EN-P - December 2009

6. Slide the safety end cap up to remove it, which exposes the

backplane and power connections.

7. Position the replacement adapter vertically above the DIN rail,

making certain the DIN rail lock is in the horizontal position.

8. Slide the adapter down, allowing the interlocking side pieces

to engage the adjacent module.

9. Press firmly to seat the adapter on the DIN rail, noting that the

adapter locking mechanism will snap into place.

10. Set the node address on the node address thumbwheel.

11. Insert the end of the terminal block opposite the handle into

the base unit, noting that this end has a curved section that
engages with the wiring base.

12. Rotate the terminal block into the wiring base until it locks

itself into place.

13. Replace the adjacent module in its base.

14. Reconnect the Ethernet cable(s) to the adapter.

15. Set the IP Address for this module.

16. Configure the adapter’s chassis size.

ATTENTION

Do not discard the end cap. Use this end cap to cover the exposed
interconnections on the last mounting base on the DIN rail. Failure to do so
could result in equipment damage or injury from electric shock.