Rockwell Automation 1756-DNB ControlLogix DeviceNet Scanner Module Installation Instructions User Manual
Page 37
ControlLogix DeviceNet Scanner Module 37
Publication
1756-IN566D-EN-P - June 2008
Indicator
State
Description
Module/
Network
(MOD/NET)
Flashing
red
(1)
Minor fault and/or connection time-out - recoverable fault
and/or one or more I/O connections are in the timed-out state.
Red
Critical fault or critical link failure - device has an
unrecoverable fault and may need to be replaced.
Failed communication device. The device has detected an
error (duplicate MAC ID or bus-off) that has rendered it
incapable of communicating on the network.
I/O
Off
Scanner is not online. Check network power.
Green
Scanner is in RUN mode, outputs are under control, and inputs
are being consumed.
Flashing
green
(1)
(1)
The flash rate of the status indicator is approximately 1 flash per second. The status indicator should
be on for approximately 0.5 seconds and off for approximately 0.5 seconds.
Scanner is in IDLE mode, outputs are not under control, and
inputs are being consumed.
OK
Off
No power applied to device. Apply chassis power. Verify
module is completely inserted into chassis and backplane.
Green
Device is operating normally. The 1756-DNB scanner module
has at least one connection to it from a controller.
Flashing
green
(2)
(2)
The flash rate of the status indicator is approximately 1 flash per second. The status indicator should
be on for approximately 0.5 seconds and off for approximately 0.5 seconds.
The device is operating correctly; however, no controller is
controlling it. Verify that the 1756-DNB scanner module is
properly configured in the controller’s I/O configuration.
Red
Device has an unrecoverable fault; repair or replace it, or
Device is in self test during power-up.