Alphanumeric Status Messages
The following table summarizes the status messages.
Alphanumeric Status Message
Status Message
Description
Run
The 1756-DNB scanner module is in Run mode.
Idle
The 1756-DNB scanner module is in Idle mode.
Auto
AutoScan is enabled and the 1756-DNB scanner module is in Idle
mode.
Flash In Progress
ControlFlash is transferring a flash image to the 1756-DNB scanner
module.
Duplicate Node
Failure
The node address of the 1756-DNB scanner module is already in
use by another device on the DeviceNet network.
Bus Off Detected
The 1756-DNB scanner module has detected errors on the
DeviceNet network and has been taken offline.
No Network Power
No DeviceNet network power is being supplied to the 1756-DNB
scanner module.
NoRX
- The 1756-DNB scanner module does not contact a scanlist.
- The 1756-DNB scanner module has not received communication
from any other device.
NoTX
The 1756-DNB module failed to transmit a message.
Reset Complete -
Change Switch
Settings
Factory default settings for the 1756-DNB module have been
restored. Set the data rate and node address rotary switches to the
desired position and restore power to the module.