Output Module Specifications
Description:
Specification: 1746-
(4)
(4)
Series A, B, and C 32-point output modules are fused to protect external wiring, one fuse per common. The fuses are
non-replaceable and are rated at 2.5A. 1746-OB32, OV32 Series D modules are not fused and have a higher current rating
than Series A, B, and C.
OB32 Series D
OV32 Series D
OB32E
Voltage Category
24
Number of Outputs
32
Points per Common
16
Operating Voltage
5 to 50V dc Source
5-50V dc Sink
10-30V dc Source
Backplane Current
Consumption
5V
0.190A
24V
0A
Isolation from Backplane
1500V ac for 1 min.
Signal Delay (max.)
on = 0.1 ms
off = 1.0 ms
on = 1.0 ms
off = 2.0 ms
Off State Leakage (min.)
1 mA
Load Current (min.)
1 mA
Continuous Current per Module (max.)
(1)
(1)
To attain the maximum Continuous Current per common rating for an OB32 Series D module, both V dc connections in a wire
group must be connected to your DC source. To attain the maximum Continuous Current per common rating for an OV32
Series D module, both dc Com connections in a wire group must be connected to your DC source.
8.0A at 0
°
C to 60
°
C
Continuous Current per Point
(max.)
at 30
°
C
0.50A
at 60
°
C
0.25A
Continuous Current per Common (max.)
4.0A at 0
°
C to 60
°
C
Continuous Current per Common Pin (max.)
2.0A at 0
°
C to 60
°
C
On State Voltage Drop (max.)
1.2V at 0.5A
Surge Current per Point
at
30
°
C
(2)
(2)
Repeatability once every second.
1.0A for 10 ms
at
60
°
C
(3)
(3)
Repeatability once every 2 seconds.
1.0A for 10 ms
Electronic Protection
No
No
Yes
Heat Dissipation Watts per Point
0.172
0.172
0.250
Heat Dissipation Watts (min.)
0.95
0.95
0.95
Heat Dissipation Total Watts
6.45
6.45
8.95