beautypg.com

Specifications, Input module specifications – Rockwell Automation 1746-XXXX SLC 500 32-Channel Digital I/O Modules Installation Instructions User Manual

Page 6

background image

6 SLC 500™ 32-Channel Digital I/O Modules

Publication 1746-IN028A-EN-P - October 2003

Specifications

Input Module Specifications

Description:

Specification: 1746-

(1)

(1)

Series A, B and C 32-point input modules are fused to protect external wiring, one fuse per common. The fuses are
non-replaceable and are rated at 2.5A. Series D 32-point input modules are not fused.

IB32

IV32

Voltage Category

24

Number of Inputs

32

Points per Common

8

Operating Voltage

15 to 30V dc at 50

°

C

15 to 26.4V dc at 60

°

C

Sink

15 to 30V dc at 50

°

C

15 to 26.4V dc at 60

°

C

Source

Backplane Current Consumption

5V

0.050A

24V

0A

Isolation from Backplane

1500V ac for 1 min.

Signal Delay (max.)

on = 3 ms
off = 3 ms

On State Voltage (min.)

15.0V dc

Off State Voltage (max.)

5.0V dc

Off State Current (max.)

1.5 mA

Nominal Input Current at 24V dc

5.1 mA at 24V dc

Heat Dissipation Watts per point

0.20

Heat Dissipation Watts (min.)

0.25

Heat Dissipation Total Watts

6.65