Specifications – Rockwell Automation 1792D-12BVT4D ArmorBlock MaXum 12 Input/4 Output Module Series B User Manual
Page 12

12 ArmorBlock MaXum 12 Input/ 4 Output Module Series B
Publication 1792D-IN004B-EN-P - August 2000
Specifications
12 Input / 4 Output Module - Cat. No. 1792D-12BVT4D
Input Specifications
Max.
Min.
Inputs per block
12 - 3 wire or dry contact PNP or NPN devices or 6 -
4 wire PNP or NPN devices
Sensor Source Current (per input)
See the graph below.
Off-Wire Sense Current
0.5mA
-
On-state Voltage
25V dc
10V dc
On-state Current
10mA
2mA
Off-state Voltage
5V dc
-
Off-state Current
-
1.5mA
Output Specifications
Max.
Min.
Outputs per block 4 sourcing outputs labeled O0 through O3
Off Peak Blocking Voltage
30V
10V
On-state Voltage Drop
1V
-
On-state Current
2.0A
-
Off-state Leakage
1.5mA
-
Module Current (all outputs)
4.0A
-
Surge Current - for 10ms,
repeatable every 2s
4.0A
-
No Load Sense Current (On-state)
0.18A
-
General Specifications
Indicators
Net/Mod Status - red/green
Logic Status - red/green
Auxiliary Power - green
Point LED - yellow/orange/red
Communication Rate
125Kbps @ 500 meters(1600 feet) for thick cable,
flat media length 375 meters (1230 feet)
250Kbps @ 200 meters(600 feet) for thick cable,
flat media length 150 meters (492 feet)
500Kbps @ 100 meters (330 feet) for thick cable,
flat media length 75 meters (246 feet)
DeviceNet Power
Voltage
Current
Refer to the graphs in the
Overview section of the
ArmorBlock I/O Family Technical
Data, pub. no.
1792-TD001B-EN-P.
25V dc max
175mA max (no sensors)
11V dc min
up to 1.6A (12
sensors @ 50mA per
sensor)
Auxiliary Power
Voltage
Current
30V dc max
4A max
10V dc min
4A max
Dimensions (assembled to base)
inches - (Millimeters)
1.9H x 2.7W x 6.85D