beautypg.com

Rockwell Automation 1792D-12BVT4D ArmorBlock MaXum 12 Input/4 Output Module Series B User Manual

Page 11

background image

ArmorBlock MaXum 12 Input/ 4 Output Module Series B 11

Publication 1792D-IN004B-EN-P - August 2000

The following table describes logic status indicators.

The following table describes auxiliary status indicators.

The following table describes I/O status indicators.

For more information on indications see the Technical Data
publication 1792-TD001B-EN-P.

Logic Status Indicators

State

Status

Off

Logic is disabled

Solid Green

Logic is enabled

Flashing Green

Local forces are applied and local logic is enabled

Auxiliary Status Indicators

Indication

Status

None

No Auxiliary power

Solid Green

Auxiliary power present

I/O Status Indicators

Function Module Status Indicator Point Indicator

1

Condition

Outputs

Green
Green
Module Status blink red
Module Status blink red
Module Status blink red
Module Status blink red

None
Yellow
Orange
Red
Orange
Red

Output not energized
Output energized
Output shorted-auto restart
Output shorted-latching
Output no load-auto restart
Output no load-latching

Inputs

Green
Green
Module Status blink red
Module Status blink red

None
Yellow
Red
Blink red

No valid input
Valid input
Short on input connection

1

Off wire on input connection

1

1

Only the first LED of each input connector will light as red when twin inputs are used.