beautypg.com

Catalog number explanation, Install the module, Set the node address – Rockwell Automation 1732D-XXXX DeviceNet ArmorBlock 16-Point I/O, Series A User Manual

Page 5

background image

DeviceNet 1732 ArmorBlock 16-Point I/O, Series A 5

Publication 1732D-IN002B-EN-E - January 2013

Catalog Number Explanation

Refer to the table for a description of the modules’ catalog numbers.

Install the Module

To install the module:

Set the node address

Mount the module

Connect the cord sets

Set the Node Address

Valid node addresses are 00 through 63.

Set the node address using either the rotary switches, RSNetWorx for DeviceNet,
DeviceNetManager, or another software configuration tool. Setting the switches at any
number from 64 through 99 lets the software have address control.

Each module is shipped set for node address 63. Remove the caps on the front of the
module to access the switches. The two switches are:

X10 (most significant digit) – left side of module

X1 (least significant digit) – right side of module

Catalog Number

Description

Network Connector

1732D-IB16M12M12

DeviceNet 24V DC 16 Input

M12 pass-through

1732D-OB16M12M12

DeviceNet 24V DC 16, 2 A Output

1732D-16CFGM12M12

DeviceNet 24V DC 16 Selectable
Points

1732D- IB161212W

DeviceNet 24V DC 16 Input M12
Weldblock

1732D-IB16M12MINI

DeviceNet 24V DC 16 Input

Mini pass-through

1732D-OB16M12MINI

DeviceNet 24V DC 16, 2 A Output

1732D-16CFGM12MN

DeviceNet 24V DC 16 Selectable
Points