General specifications – Rockwell Automation 1732D-XXXX DeviceNet ArmorBlock 16-Point I/O, Series A User Manual
Page 18

18 DeviceNet 1732 ArmorBlock 16-Point I/O, Series A
Publication 1732D-IN002B-EN-E - January 2013
Isolation voltage
50V (continuous), Basic Insulation Type, Outputs and Output
Power to Network
No isolation between individual Outputs or between Outputs
and Output power
Type tested at 707V DC for 60 s
Surge current per output, max
1.2 A for 10 ms, repeatable every 2 s (1732D-16CFGM12y)
4.8 A for 10 ms, repeatable every 2 s (1732D-OB16M12y)
Pilot duty rating
Not rated
General Specifications
Attribute
Value
Voltage, auxiliary power, max
30V DC
Voltage, auxiliary power, min
12V DC
Voltage, DeviceNet power, max
25V DC
Voltage, DeviceNet power, min
11V DC
Current, auxiliary power input, max
900 mA
Current, auxiliary power, max
8 A
Current, sensor source, per input, max
50 mA
Current, sensor source, per module, max 800 mA
Communication rate
125 Kbps @ 500 m (1640 ft) for thick cable,
flat media length 375 m (1230 ft)
250 Kbps @ 200 m (600 ft) for thick cable,
flat media length 150 m (492 ft)
500 Kbps @ 100 m (330 ft) for thick cable,
flat media length 75 m (246 ft)
DeviceNet current
100 mA (75 mA for 1732E-IB16M12y)
Indicators
1 green/red module status
1 green/red network status
1 green auxiliary power
16 yellow input/output status
Enclosure type rating
Meets IP65/66/67/69K (when marked), and NEMA 4X/6P with
recepticle dust caps or cable termination
DeviceNet 1732 ArmorBlock 16-Point I/O, Series A - 1732D-OB16M12M12,
1732D-OB16M12MINI 1732D-16CFGM12M12, 1732D-16CFGM12MINI
Attribute
Value